Skip to main content

Eastron SDM630

Status: Vendor Confirmed · Register points: 97 · Transports: Modbus RTU

A curated ModDef profile for the Eastron SDM630. Import it as eastron.sdm630 or load the .moddef.yaml directly.

Connect to one over Web Serial and watch its values live in the device dashboard.

Usage​

Load the profile, bind a transport, and read a point by name. The runtime applies the offset, scaling, byte order, and sentinels from the definition.

doc, _ := moddef.Load("eastron-sdm630.moddef.yaml")
dev, _ := client.New(doc, "eastron-sdm630", transport) // your modbus.Transport
v, _ := dev.ReadPoint(ctx, "voltage_l1_n")
fmt.Println(v)

Commands​

Multi-step register procedures (spec §11.7) this profile defines — write params, arm a trigger, poll for completion, then read the result. Run one with your language's command executor (RunCommand, runCommand, run_command, or md_cmd_begin/md_cmd_tick in C/C++).

set_system_type — Set Wiring System Type​

Change the meter's wiring system type behind the password gate. Enters the password at 40015's companion register 40025, writes the new system type (1 = 1p2w, 2 = 3p3w, 3 = 3p4w), then re-locks by writing to the Password Lock register, which is the document's option (b) for reapplying the lock. The default password is 0000. Both params are IEEE-754 floats like every other register on this meter.

Params

FieldTypeRequired
passwordFLOAT32yes
system_typeFLOAT32yes

Results

FieldType
system_typeFLOAT32
lock_statusFLOAT32

Measurands​

The 10 semantic quantities this device reports, each linked to the measurand catalog. Query a device by measurand instead of a raw point when you want portable code.

Base quantityNameUnitDescription
voltageVoltageVRMS voltage; qualify with phase_ref (L1_N, L1_L2, ...)
currentCurrentARMS current; qualify with phase_ref / direction
active_powerActive PowerWInstantaneous real power
apparent_powerApparent PowerVAInstantaneous apparent power
reactive_powerReactive PowervarInstantaneous reactive power
power_factorPower Factor1 (ratio)Ratio of real to apparent power (dimensionless)
frequencyFrequencyHzGrid frequency
energy_activeActive EnergyWhCumulative active energy register
energy_apparentApparent EnergyVAhCumulative apparent energy register
energy_reactiveReactive EnergyvarhCumulative reactive energy register

Source​